MTU Generator Sets

MTU Series 2000 and 4000 engines pack more power into less space than almost anything else on the market, which is what data centre and naval projects pay for.

MTU Germany diesel engines · packaged in Fujian, China
Power Range880 – 3,863 kVA
Frequency50 Hz / 60 Hz
EmissionStage V · Tier 4F
Engine Platform

Why specify a MTU engine

MTU (Rolls-Royce Power Systems) sits at the top of the performance pyramid: high power density, fast load acceptance and best-in-class transient response. Series 1600, 2000 and 4000 engines are specified for mission-critical data centres and offshore installations.

  • Outstanding load acceptance (G3 / G4 class)
  • Containerised packages up to the top of the range
  • Full Stage V compliance with SCR aftertreatment
MTU 发动机特写图 / MTU engine close-up
Model Tables

MTU powered generator sets

Every rating we list for this engine platform, with the engine model for each.

50 Hz ratings for the MTU platform — ISO 8528-1, kW at 0.8 power factor. Each model has a downloadable data sheet (EN); weights and drawings are issued with the quotation.
ModelStandby Power (kVA)Standby Power (kW)Prime Power (kVA)Prime Power (kW)Engine ModelData Sheet
CM-MT12501,2501,0001,12590018V2000G65[EN]
CM-MT13751,3751,1001,2501,00018V2000G26F[EN]
CM-MT15001,5001,2001,3501,08012V4000G14RF[EN]
CM-MT1800C1,8001,4401,6251,30012V4000G23[EN]
CM-MT1800D1,8001,4401,6251,30012V4000G14F[EN]
CM-MT2000C2,0001,6001,8121,45012V4000G63[EN]
CM-MT2000D2,0001,6001,8121,45012V4000G24F[EN]
CM-MT2200C2,2001,8002,0001,64016V4000G23[EN]
CM-MT2200D2,2001,8002,0001,64016V4000G14F[EN]
CM-MT2500C2,5002,0002,2501,80016V4000G63[EN]
CM-MT2500D2,5002,0002,2501,80016V4000G24F[EN]
CM-MT2750C2,7502,2002,5002,00020V4000G23[EN]
CM-MT2750D2,7502,2002,5002,00020V4000G14F[EN]
CM-MT3000C3,0002,4002,7502,20020V4000G63[EN]
CM-MT3000D3,0002,4002,7502,20020V4000G24F[EN]
CM-MT3250C3,2502,6003,0002,40020V4000G63L[EN]
CM-MT3250D3,2502,6003,0002,40020V4000G34F[EN]
CM-MT3575D3,5752,8603,2502,60020V4000G44F[EN]
60 Hz ratings for the MTU platform — ISO 8528-1, kW at 0.8 power factor. Each model has a downloadable data sheet (EN); weights and drawings are issued with the quotation.
ModelStandby Power (kVA)Standby Power (kW)Prime Power (kVA)Prime Power (kW)Engine ModelData Sheet
CM-MT988987.579090072012V2000G85[EN]
CM-MT11251,1259001,031.2582516V2000G45[EN]
CM-MT12501,2501,0001,137.591016V2000G85[EN]
CM-MT15001,5001,2001,343.751,07518V2000G85[EN]
CM-MT1925C1,9251,5401,7501,40012V4000G43[EN]
CM-MT1925D1,9251,5401,7501,40012V4000G14S[EN]
CM-MT2250C2,2501,8002,037.51,63012V4000G83[EN]
CM-MT2250D2,2501,8002,037.51,63012V4000G24S[EN]
CM-MT2600C2,6002,0802,362.51,89016V4000G43[EN]
CM-MT2600D2,6002,0802,362.51,89016V4000G14S[EN]
CM-MT2938C2,937.52,3502,662.52,13016V4000G83[EN]
CM-MT2938D2,937.52,3502,662.52,13016V4000G24S[EN]
CM-MT3163C3,162.52,5302,8752,30020V4000G43[EN]
CM-MT3163D3,162.52,5302,8752,30020V4000G14S[EN]
CM-MT3500C3,5002,8003,181.252,54520V4000G83[EN]
CM-MT3500D3,5002,8003,181.252,54520V4000G24S[EN]
CM-MT3863C3,862.53,0903,512.52,81020V4000G83L[EN]
CM-MT3863D3,862.53,0903,512.52,81020V4000G44S[EN]

Both 50 Hz and 60 Hz builds are listed. Model codes carry the standby rating and, where two builds share a rating, a trailing letter.

MTU publishes both continuous and standby ratings to ISO 8528, and the gap between them is narrow. Derate follows the Series 4000 application manual: about 3 % per 100 m of altitude and 1 % per 5 °C above the reference ambient.

Sizing a MTU set?

Tell us the footprint you actually have, not the rating you want. MTU sets are compact for their output but they need more combustion air and exhaust clearance than the enclosure dimensions suggest, and we would rather resolve that before the concrete is poured.

Configuration Options

Where an MTU set goes

High power density means high heat rejection, so the package matters as much as the engine.

MTU builds are dense, so we treat the enclosure as an engineering problem rather than a finishing option. Series 2000 units up to about 1,200 kVA fit a reinforced acoustic canopy. Series 4000 units almost always go into a container or a purpose-built plant room with a remote radiator, because the charge-air cooling and exhaust volume will not fit a canopy at that rating.

MTU 机型 Container 配置图 / MTU in Container configuration
Typical power rangeUp to 4,000 kVA
Enclosure10 / 20 / 30 / 40 / 45 ft container
Ingress protectionIP54 (IP55 optional)
Best suited toSeries 4000, 1,500 kVA and above, data centres

Full Containerized specification

MTU 机型 Silent 配置图 / MTU in Silent configuration
Typical power range10 – 4,000 kVA
EnclosureGalvanised acoustic canopy
Ingress protectionIP54
Best suited toSeries 2000 in hospitals, banks and urban standby

Full Silent Type specification

MTU 机型 Open 配置图 / MTU in Open configuration
Typical power range10 – 4,000 kVA
EnclosureNone — open skid
Ingress protectionIP21 (control panel IP54 optional)
Best suited toMarine and plant-room retrofits with remote cooling

Full Open Type specification

Cross Reference

Compare other engine brands

Where the budget is set by a tender rather than a technical brief, a Baudouin or Yuchai set of similar rating will land 20–30 % lower on unit price.

品牌对比展示图 / multi-brand comparison visual

Already running a MTU set?

Series 2000 and 4000 injectors, high-pressure pumps, turbochargers and the ADEC control modules are available to order, with genuine parts carrying MTU documentation.

Questions

MTU sets, answered plainly

The three things buyers ask us most about this engine platform.

Power density and parts pricing. You pay for a smaller footprint and a genuine service organisation, and the replacement parts carry a premium that reflects that.

Yes. Series 4000 sets parallel through the MTU or a third-party switchgear, and we supply the droop and load-sharing settings with the commissioning documentation.

Either a container-mounted radiator with adequate louvre area or a remote radiator. We size the louvres against the engine's heat rejection, not against the container size.